21
turns one ON then OFF, the specified Link Unit will be restarted. Other con-
trol bits are OFF until set by the user.
Word(s) Bit(s) Function
236 00 to 07 Node loop status output area for operating level 0 of
SYSMAC NET Link System
08 to 15 Node loop status output area for operating level 1 of
SYSMAC NET Link System
237 00 to 07 Completion code output area for operating level 0 following
execution of SEND(90)/RECV(98) SYSMAC
LINK/SYSMAC NET Link System
08 to 15 Completion code output area for operating level 1 following
execution of SEND(90)/RECV(98) SYSMAC
LINK/SYSMAC NET Link System
238 to 241 00 to 15 Data link status output area for operating level 0 of
SYSMAC LINK or SYSMAC NET Link System
242 to 245 00 to 15 Data link status output area for operating level 1 of
SYSMAC LINK or SYSMAC NET Link System
246 00 to 15 Not used
247 to 250 00 to 07 PC Link Unit Run Flags or data link status for operating
level 1
08 to 15 PC Link Unit Error Flags or data link status for operating
level 1
251 00 to 15 Remote I/O Error Flags
252 00 SEND(90)/RECV(98) Error Flag for operating level 0 of
SYSMAC LINK or SYSMAC NET Link System
01 SEND(90)/RECV(98) Enable Flag for operating level 0 of
SYSMAC LINK or SYSMAC NET Link System
02 Operating Level 0 Data Link Operating Flag
03 SEND(90)/RECV(98) Error Flag for operating level 1 of
SYSMAC LINK or SYSMAC NET Link System
04 SEND(90)/RECV(98) Enable Flag for operating level 1 of
SYSMAC LINK or SYSMAC NET Link System
05 Operating Level 1 Data Link Operating Flag
06 Host Computer to Rack-mounting Host Link Unit Level 1
Error Flag
07 Rack-mounting Host Link Unit Level 1 Restart Bit
08 CPU-mounting Host Link Unit Error Flag
09 CPU-mounting Host Link Unit Restart Bit
10 Not used.
11 Forced Status Hold Bit (CPU11-E only)
12 I/O Status Hold Bit
13 Rack-mounting Host Link Unit Level 0 Restart Bit
14 Not used.
15 Output OFF Bit
SR Area Section 3-4